3Com 3C523
@6042.ADF
- EtherLink/MC Ethernet Adapter
3C523X.EXE
V3.3 EtherDisk for ELMC/TP (8193-04)�
3C523N.EXE
EtherDisk, 3C523 family w/latest patches, V3.4.�
00005247�
MC-TP Xceivers and Possible Problems in Max-Length Runs
3C523 Etherlink/MC
3C523 Etherlink/MC TP
Late 3C523 Etherlink/MC
Older versions not compatible with 486+
3C523 ADF Sections
3C523 Etherlink/MC
3C523 Etherlink/MC TP
Late 3C523 Etherlink/MC
1E RPL socket
2E N82586
2A,B CXK5864BM-10L
6B,7B 3Com 6408-01
7E NSDP8391AV
8E Motorola MC10116L |
LP1 Neom Lamp
P2 AUI port
P3 BNC port
Y1 20.00000 MHz osc
Y3 16 MHz osc
1 |
� I found two of these in a 3172 Interconnect Controller. Marked
"(C) 1990 3Com" on the front.
Setting Jumpers on EtherLink/MC TP Adapter
IMPEDANCE
����� a.� Use a test device to verify
the characteristic impedance of your�
�������� cable from the wiring
closet to the station.
����� b.� Choose the setting closest
to that characteristic impedance.
��������� Default Setting:�
100 ohms
��������� Alternative
Settings:� 75 ohms, 150 ohms
RECEIVE THRESHOLD, LINK BEAT, EQUALIZATION,
TRANSMIT LEVEL, and DC SIGNAL jumpers, refer to Table 1.�
�Table 1.� Jumper Settings for 10BASE-T and Non-10BASE-T Hubs
����������������������������������������
HP StarLAN 10,
��������������������������
SynOptics��� AT&T StarLAN 10,�
�������������
10BASE-T���� LattisNet��� DAVID Systems����
BULL Hub 10
�������������
(default)� (non-10B-T)��� (non-10B-T)������
(non-10B-T
Link Beat�������
ON����������� OFF������������
OFF������������
OFF
Equalization���� TX�����������
RX�������������
TX�������������
RX
DC Signal�������
OFF���������� ON�������������
OFF������������
OFF
Xsmit Level����� NORM���������
LOW������������
NORM�����������
LOW
Rcv Thres�������
NORM��������� LOW������������
NORM�����������
LOW-
3c523 Versions
not Compatible with 486+
�� The "old" 3C523 have a copyright date of 1987 on them
and will only work properly in a 286 or 386. From my expiriences, it will
only let the first 8MB RAM be usable no matter how much RAM you have installed.�
The newer revision will have a 1990 or 1991 date on it.�
From Peter
�� Fact is: some series of the older Ethernet/MC have a microcode
incompatible with 486-processors. (Bus signalling most likely - haven't
tested that in depth)�
�� Symptom: they worked fine as long as they were used in
Mod. 70/80 - but when the customer swapped them to the new bought 76/77
they went belly up and did not even pass the DOS-based diags test.�
�� These are older ones produced before 1990 - but ironically
not all old cards are automatically affected. There was a diagnostic program
available from 3COM (I think it came with the revised E/MC) which checks
the microcode level and warns for possible incompatibilities. In addition
some of the setup / diags and driver software had a problem with later
OS-versions (did not run properly under PC-DOS 4.x and above due to "version
conflict"). Whatever.�
Component Differences, Old vs. New
>Is that a 3C523? ISTR that those (or most of them, anyway) wouldn't�
work properly in anything� than a 386.�
The original 3C-523 has a limitiation - the later ones (3C-523B) hasn't.
Roughly the two can be differed by looking on the board:�
Old Model
�� Round "transformer", many "through-hole" chips and "classical"
resistors, long DIL "i" (Intel) 82586 MCU, "(C) 1987 3Com" at frontside�
New Model
� Square "3Com" transformer, mainly SMD chips with square QFP
"i" Intel 82586 MCU, "(C) 1991 3Com" along the bottom/front.�
The old one will most likely not run with anything bigger than a 386DX
- the new one hasn't got this problem. Works with 486 and Pentium. Both
cards have the same card-ID and use the same ADF, so you cannot tell which
is which by the ID only.�
AdapterId 6042
3Com EtherLink/MC Ethernet Adapter
Enable/Disable Adapter
�� Use the Disabled setting if you are not using the adapter
and enabling it causes a conflict with another device.
���� <" Adapter Enabled
>, Adapter Disabled�
I/O Address Range
�� I/O addresses used by EtherLink/MC. The addresses in this
range cannot be used by another installed device
��� <"� 300 to� 307 ">, 1300 to 1307, 2300
to 2307, 3300 to 3307�
Interrupt Level
�� Interrupt level used by EtherLink/MC. This adapter's interrupt
level can be shared with another device.� You may be able to improve
performance
by selecting a level that is not used by any other device.
�� <" Channel 3 " ( INT 3)>,
7, 9, 12
Packet Buffer RAM Address Range
�� RAM and ROM addresses used by EtherLink/MC.� The
addresses in this range cannot be used by any other installed device.�
The range represents
16K bytes of RAM addresses followed by 8K bytes of ROM addresses
�� <" 0C0000 to 0C5FFF " >,
0D0000 to 0D5FFF , 0D8000 to 0DDFFF
Transceiver Type
�� Transceiver used by EtherLink/MC. If you have a thin Ethernet
network and wish to connect to the adapter's round BNC connector or you
have a twisted pair Ethernet network and wish to connect to the adapter's
8 pin
RJ45 connector (EtherLink/MC TP only), select On-Board.� If you
have a drop cable from an external transceiver and wish to attach to the
adapter's 15 pin AUI connector, select External.
�� <" On-Board (BNC or RJ45) ">,
External (AUI)
Diagnostics Warnings
�� The computer containing the EtherLink/MC adapter to be
tested must be running DOS.� If this computer is an operating server,
notify all users of the server to save their work and log out from the
network.� The diagnostic program disrupts the normal operation of
the server, and work that is not saved may be lost.� The diagnostic
tests do not function properly if you run them after booting your system
with NetBIOS installed. Please start your computer with a standard boot
diskette that does not contain a network driver.
�� NOTE:� If Group
3 tests are running while the computer is connected to an active network,
intermittent packet exchange failures may occur before the tests are done.�
These failures can be avoided by running Group 3 tests on an inactive network
in which only the computer being tested and the echo server are connected.
ELMC Fails Diagnostics
If the EtherLink/MC adapter diagnostic tests fail, the adapter may
not be
defective.� Check the following:
1.� Make sure adapter is completely seated in slot.
2.� Inspect all cables and connections.
3.� If you are running the Group 2 tests, make sure adapter is
securely connected to a loopback plug (coax version only) or to a properly
cabled inactive network.
4.� If you are running the Group 3 tests, make sure adapter is
securely connected to a properly cabled inactive network and that an echo
server is set up on the network.
5.� Make sure that none of the adapter settings conflict with
any other��� peripheral or software program (such as 3Com's
Extended Memory Manager) installed in the computer.� For a list of
system resources commonly used by other peripherals, select "Additional
Adapter Information" from the main menu, then "System Resources" from the
Information submenu.�
6.� Make sure that the transceiver type selected is correct.
7.� Running tests while connected to an active network can cause
intermittent failures.� These failures can be avoided by using an
inactive network on which only the computer being tested (and an echo server
if running the Group 3 tests) is connected.
8.� If you installed an EtherLink/MC TP adapter, check the LEDs
on the back-plate of the adapter.� The yellow (ACT) LED is on when
there is data
�transmission activity on the adapter.� This light will go
on during the Group 2 and Group 3 tests.� The green (LNK) LED will
be on when there is a correct connection between the adapter and the hub.�
If the link pulse jumper is in the OFF position, the green LED will be
on whether or� not there is a connection.
9.� If you have installed an EtherLink/MC TP adapter, make sure
that the�
��� settings for the following jumpers are correctly
configured for the hub:
������� RECEIVE THRESHOLD
������� DC SIGNAL
������� LINK PULSE
������� EQUALIZATION
������� WIRE IMPEDANCE
������� TRANSMIT LEVEL
���� For information on setting these jumpers,
select "Additional Adapter��� Information" from the main
menu, then "Twisted-pair Options" from the���� Information
submenu.
10. The computer slot may be defective.� Install adapter in�
another slot and run tests again.
11. The computer in which the adapter is installed may be defective.
Install the adapter in a known functioning computer and re-run the tests.
�12. The loopback plug� may be defective.� Try a different
loopback plug.
13. Replace failed adapter with a known good EL/MC adapter with the
same jumper settings.� If the second EL/MC adapter fails, something
is wrong with the test environment, not with the adapter.
9595 Main Page
|